The Enset Titan 250 is a higher-capacity version of the Titan series industrial inverter heat pump using the natural refrigerant R290, designed for heating, cooling, and domestic hot water production in larger commercial, industrial, and residential buildings. A dual inverter DC compressor with an extended operating range and dual fans deliver high performance with stable, quiet operation.
Key Advantages
- Rated heating capacity of 50 kW under A7/W35 conditions, up to 80 kW at increased output.
- Natural refrigerant R290 with an extremely low global warming potential (GWP).
- Energy efficiency class A+++ at a flow temperature of 35 °C and A++ at 55 °C.
- Operation at outdoor temperatures from −25 °C to 43 °C.
- Outlet water temperature up to 70 °C for underfloor heating, radiator heating, and hybrid operation with a gas boiler.
- Two high-efficiency DC fans for greater airflow capacity.
- High-efficiency SS316 heat exchanger, resistant to corrosion.
- Patented superheat control technology (EEV) and advanced defrosting technology with pressure and temperature compensation.
- Compressor pre-heating system for reliable start-up at low temperatures.
- Safety NDIR R290 refrigerant leak detector (±2.5% LFL accuracy) with an ATEX-rated exhaust fan.
- Smart control: weather-compensated operation, SG Ready, remote control via the WarmLink app (4G-DTU + WiFi).
- Centralized management of up to 32 units from a single display.
| Parameter | Value |
|---|---|
| Model | Enset Titan 250 |
| Refrigerant / charge | R290 / 3800 g × 2 |
| Heating Condition 1 – ambient temp. 7 °C/6 °C, water 30 °C/35 °C | |
| Nominal capacity | 50 kW |
| Heating capacity range | 22.09–80.00 kW |
| Power input range | 6.00–22.00 kW |
| COP | 3.64–4.60 |
| Current input range | 9.55–35.05 A |
| Heating Condition 2 – ambient temp. 2 °C/1 °C, water 30 °C/35 °C | |
| Heating capacity range | 16.16–59.27 kW |
| Power input range | 5.50–18.98 kW |
| COP | 3.12–3.51 |
| Current input range | 8.40–30.84 A |
| Heating Condition 3 – ambient temp. −7 °C/−8 °C, water 50 °C/55 °C | |
| Heating capacity range | 12.03–43.00 kW |
| Power input range | 7.63–22.80 kW |
| COP | 1.89–2.79 |
| Current input range | 11.68–35.04 A |
| Cooling Condition – ambient temp. 35 °C/24 °C, water 12 °C/7 °C | |
| Cooling capacity range | 17.18–62.00 kW |
| Power input range | 7.00–25.68 kW |
| EER | 2.47–3.65 |
| Current input range | 11.18–41.00 A |
| Hot Water Condition – ambient temp. 20 °C/15 °C, water 15 °C/55 °C | |
| Hot water capacity range | 27.27–100.00 kW |
| Power input range | 6.86–25.17 kW |
| COP | 3.21–4.65 |
| Current input range | 11.67–42.80 A |
| Max. hot water capacity | 2,150 L/h |
| ErP energy class (35 °C) | A+++ |
| ErP energy class (55 °C) | A++ |
| SCOP at 35 °C | 4.58 |
| SCOP at 55 °C | 3.67 |
| SCOP at 65 °C | 3.16 |
| Max. power input | 36 kW |
| Max. current input | 45.00 A |
| Power supply | 380–415 V / 3N / 50 Hz |
| Sound pressure level (1 m) | 56 dB(A) |
| Sound power level (EN 12102) | 73 dB(A) |
| Operating ambient temperature range | −25 °C to 43 °C |
| Max. outlet water temperature | 70 °C |
| Number of fan motors | 2 |
| Water connection | G2″ |
| Rated water flow | 8.60 m³/h |
| Rated water pressure drop | 45 kPa |
| Available external static head | 2 m |
| CO₂ equivalent | 0.0228 t |
| Net weight | 635 kg |
| Gross weight | 693 kg |
| Unit dimensions (L×W×H) | 1,965 × 1,060 × 1,900 mm |
| Packing dimensions (L×W×H) | 2,055 × 1,080 × 2,030 mm |
| Units per 40′ HQ container | 11 pcs |
| Ident | to be verified upon product entry |